Copper Tube Material

Copper phosphorus deoxidised (DHP-Cu), having minimum copper content 99,90% and P=0,015% - 0,040%.

Quality Marks

REFRIGERATION PIPES: ΑΕΝΟR  TÜV, GL, VIK.

Mechanical Properties

TemperEN 12735 ClassificationMinimum Tensile strength Rm (MPa)Min elongation, A%
SoftR-22022040

 

Insulation Technical Properties

MATERIAL

PE-X foam

DENSITY ACCORDING TO DIN 53420 ASTM D 1667

30-33 Kg/m3

THERMAL CONDUCTIVITY COEFFICIENT (λ) ACCORDING TO ASTM C 335

0,039 W/m.K  

VAPOUR-WATER DIFFUSSION RESISTANCE COEFFICIENT (μ) ACCORDING TO ISO 12572

> 9.000  

WORKING TEMPERATURE

-80oC to +110oC

FIRE RESISTANCE

EN 13501–1, Class B or Class E, DIN 4102, B2, BS 476, NF P 92 501-M1

RESISTANCE TO CHEMICAL AGENTS ACC. TO ASTM 543-56 T

Very good

SOUND ABSORPTION ACC. TO DIN 4109 300-2500Hz

~60%

DIMENSIONAL STABILITY ACCORDING TO ISO 2796 FOR TEMPERATURES UP TO 1000C

<5%

Values are listed, as obtained under standard laboratory conditions and may be amended, without prior notice.

Standard Pair Dimensions (Coils 15m, 25m, 30m Long)

Copper tube external diameter Inch Copper tube external diameter mmCopper tube wall thickness mmOverall external diameter with 9mm thick insulation mm
¼-3/86,35-9,520,80-0,8024,4-27,5
¼-1/26,35-12,70,80-0,8024,4-30,7
¼-5/86,35-15,880,80-1,0024,4-33,9
¼-3/46,35-19,050,80-1,0024,4-37,10
3/8-1/29,52-12,70,80-0,8027,5-30,7
3/8-5/89,52-15,880,80-1,0027,5-33,9
3/8-3/49,52-19,050,80-1,0027,5-37,1
½-3/412,7-19,050,80-1,0030,7-37,1
 

Other sizes and special packaging in pallets or cardboard boxes are available upon request.

Pair Diameters

1/4" + 3/8"

1/4" + 1/2"

1/4" + 5/8"

1/4" + 3/4"

3/8" + 1/2"

3/8" + 5/8"

3/8" + 3/4"

1/2" + 3/4"

Appropriate also for the new Green Refrigeration Units

According to the European Standard EN12735-1:2010, as well as current market requirements, laid down by the use of new generation of refrigerants, including HFCs and HFOs, adopted by all major manufacturers of refrigeration and air conditioning units the following standardisation is applied to TALOS® ACR ECUTHERM 2TM copper tubes:

  • For an external diameter of 1/4” to 1/2”, the wall thickness is standardised at 0,80 mm
  • For an external diameter of 5/8” to 3/4”, the wall thickness is standardised at 1,00 mm